Change of defrost condition (Jo)
Press “PSW1” and select the setting condition “1” at the change of defrost condition “Jo”.
Example for RAS-(3-12)H(V)N(P/C)(1)(E):
Settingcondition
StandardSpecications(factorydefaultstate) Heatingspecication
Functionselectionsetting
Jo:0 FunctionselectionsettingJo:1
Temperature
conditions under
defrosting
operation
Defrosting
operation
start area
Defrosting
operation
stop area
Outdoor
temperature
(ºC)
Outdoor evaporat-
ing temperature (ºC)
(pipe)
Outdoor
evaporating
temperature (ºC)
(pipe)
Defrosting
operation
stop area
Defrosting
operation
start area
Outdoor
temperature
(ºC)
Example for RAS-(2.0-2.5)HVNP1 / RAS-3HVNC1
Settingcondition
StandardSpecications(factorydefaultstate) Heatingspecication
Functionselectionsetting
Jo:0 FunctionselectionsettingJo:1
Temperature
conditions under
defrosting
operation
-4.6
Defrosting
operation
start area
Defrosting
operation
stop area
Outdoor
temperature
(ºC)
Outdoor evaporat-
ing temperature (ºC)
(pipe)
Outdoor evaporat-
ing temperature (ºC)
(pipe)
Defrosting
operation
stop area
Defrosting
operation
start area
Outdoor
temperature
(ºC)