Fixing on demand function (dE)
Press “PSW1” and select the setting condition “1”, so that the xing of demand function “dE” can be set.
However, it is not necessary to short-circuit the demand input terminals on the outdoor unit PCB. (Refer to section “6.1.4
Descriptionofoptionalsignals”in the input “e.Currentcontroldemand(5/6/7/8/9/10)”)
The tables below is the limit of the running current for this function.
RAS-(2-2.5)HVNP1 / RAS-3HVNC1
RAS-3HVNP1E / RAS-(4-12)H(V)NP1(E)/
RAS-(8-12)HN(P/C)(E)
Controlfunctionnumber(*)
Demandrunningcurrent
control
1 to 4 100%
5 60%
6 80%
7 100%
Controlfunctionnumber(*)
Demandrunningcurrent
control
1 to 5, 10 100%
6 60%
7 70%
8 80%
9 100%
RAS-(4-6)H(V)NC1E
Controlfunctionnumber(*)
Demandrunningcurrent
control
1 to 5, 11 100%
6 40%
7 60%
8 70%
9 80%
10 100%
(*) This function can be activated when demand function
is selected at one of the input terminal indications i1, i2
and i3. In case that multiple demand functions are set at
the input terminal indicationsi1, i2 and i3, the demand
running current is selected as below.
5 > 6 > 7 (Control function number)
(*) This function can be activated when demand function
is selected at one of the input terminal indications i1,
i2 and i3. In case that multiple demand functions are
set at the input terminal indicationsi1, i2 and i3, the
demand running current is selected as below.
6 > 7 > 8 > 9 (Control function number)
• Demand Control.
Adopting self-demand function which drastically decreases power consumption has largely improved energy-saving.
Power setting
Selectable from 100%, 80%, 70% and
60% of the rated power consumption
for cooling operation.
Excesive power supply
consumption exceeding the power
setting range is
restricted
Morning
Daytime
Operating hours
Power consumption
Nigth
Maximum efciency is secured
within the power setting range