EasyManua.ls Logo

Hitachi RAS-(4-12)HNP(1)(E) - Fixing on Demand Function (De)

Hitachi RAS-(4-12)HNP(1)(E)
498 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 Optional functions
179
SMGB0087 rev.0 - 12/2013
6
Fixing on demand function (dE)
Press “PSW1” and select the setting condition “1”, so that the xing of demand function “dE” can be set.
However, it is not necessary to short-circuit the demand input terminals on the outdoor unit PCB. (Refer to section “6.1.4
Descriptionofoptionalsignals”in the input “e.Currentcontroldemand(5/6/7/8/9/10)”)
The tables below is the limit of the running current for this function.
RAS-(2-2.5)HVNP1 / RAS-3HVNC1
RAS-3HVNP1E / RAS-(4-12)H(V)NP1(E)/  
RAS-(8-12)HN(P/C)(E) 
Controlfunctionnumber(*)
Demandrunningcurrent
control
1 to 4 100%
5 60%
6 80%
7 100%
Controlfunctionnumber(*)
Demandrunningcurrent
control
1 to 5, 10 100%
6 60%
7 70%
8 80%
9 100%
RAS-(4-6)H(V)NC1E
Controlfunctionnumber(*)
Demandrunningcurrent
control
1 to 5, 11 100%
6 40%
7 60%
8 70%
9 80%
10 100%
(*) This function can be activated when demand function
is selected at one of the input terminal indications i1, i2
and i3. In case that multiple demand functions are set at
the input terminal indicationsi1, i2 and i3, the demand
running current is selected as below.
5 > 6 > 7 (Control function number)
(*) This function can be activated when demand function
is selected at one of the input terminal indications i1,
i2 and i3. In case that multiple demand functions are
set at the input terminal indicationsi1, i2 and i3, the
demand running current is selected as below.
6 > 7 > 8 > 9 (Control function number)
Demand Control.
Adopting self-demand function which drastically decreases power consumption has largely improved energy-saving.
Power setting
Selectable from 100%, 80%, 70% and
60% of the rated power consumption
for cooling operation.
Excesive power supply
consumption exceeding the power
setting range is
restricted
Morning
Daytime
Operating hours
Power consumption
Nigth
Maximum efciency is secured
within the power setting range

Table of Contents

Related product manuals