7 Test run
196
SMGB0087 rev.0 - 12/2013
7.3 Testrunprocedureusingtheremotecontrolswitch(PC-ARF)
DisplayPart
A/C
COOL
HIGH
LOUV. ADJ
Meeting Room
MODE SPEED LOUV. TEMP
FLTR
Motion Sensor is activated
OK
?
FilterSignIndicator
FLTR
It is indicated at the set period for lter
cleaning.
OperationLockIndicator
It is indicated when the operation lock
function is set.
ScheduleTimerIndicator
It is indicated when the schedule timer
function is set.
SwingLouver
Indicator
FanSpeedIndicator
ArrowKey EnterKey
RUN/STOPSwitch
RunIndicator
It lights while the unit is
operated, and it ashes in
an abnormal conditions.
OperationMode
Indicator
The indications of “HEAT”
and “AUTO” are indicated
only for the heat pump type
models.
OperationGuide
Indicator
“Central Control” is
indicated while the remote
control operation is
prohibited.
RoomName
Indicator
OperationPart
SettingTemperature
Indicator
HelpSwitch
To display Help Menu.
ReturnSwitch
To return to the previous
screen.
MenuSwitch
To display Menu.
MotionSensorIndicator
It is indicated only for the air
panel with motion sensor.
1 Turn ON the power supply for all the indoor units.
2 For the models with the auto-address function, wait for 3 minutes approximately. The addressing is automatically per-
formed. (There is a case that 5 minutes is required according to the setting condition.) After that, select using language
from “Menu”. Refer to the operation manual for details.
3 Press and hold “
” (menu) and “ ” (return) simultaneously for at least 3 seconds.