8 Troubleshooting
282
SMGB0087 rev.0 - 12/2013
Contents of the check mode 2
When more than three indoor units are connected to one remote control switch, the latest data of only the rst three indoor
units that are connected serially are displayed.
If you press the part “” of the TEMP switch, the next display appears. If you press the part “” of the TEMP switch, the
previous display appears.
Temperature indication
Indication of the category code
Indication of the temperature, etc
1
Indoor unit air inlet temperature at
thermistor (°C)
91
23
Corresponds to check mode 1 “b2”
2
Indoor unit discharge air tempera-
ture at thermistor (°C)
92
50
Corresponds to check mode 1 “b3”
3
Indoor unit heat exchanger liquid
pipe temperature
(freeze protection) (°C)
93
25
Corresponds to check mode 1 “b4”
4 Outdoor temperature (°C)
94
12
Corresponds to check mode 1 “b6”
5
Indoor unit heat exchanger gas
pipe temperature (°C)
95
25
Corresponds to check mode 1 “b7”
6
Evaporating temperature at
heating (°C)
96
03
Corresponds to check mode 1 “b8”
7 Control information
97
--
Corresponds to check mode 1 “b9”
8
Discharge gas temperature at the
top of compressor chamber (°C)
98
45
Corresponds to check mode 1 “bA”
Compressor pressure/frequency indication
9
Discharge pressure (high)
(x 0.1 MPa)
9g
18
Corresponds to check mode 1 “H1”
10
Suction pressure (low)
(x 0.01 MPa)
9A
04
Corresponds to check mode 1 “H2”
11 Control information
96
44
Corresponds to check mode 1 “H3”
12 Operating frequency (Hz)
9C
44
Corresponds to check mode 1 “H4”
Expansion opening indication
13
Indoor unit expansion valve
opening (%)
9d
20
Corresponds to check mode 1 “L1”
14
Outdoor unit expansion valve mv1
opening (%)
9E
gg
Corresponds to check mode 1 “L2”
Estimated electric current indication
15 Compressor running current (A)
9
20
Corresponds to check mode 1 “P1”
Returns to temperature indication