2 Unit Installation
17
SMGB0087 rev.0 - 12/2013
2
2.2 Transportationofoutdoorunit
D A N G E R
Donotputanyforeignmaterialintotheoutdoorunitandchecktoensurethatnoneexistsintheoutdoorunit
beforetheinstallationandtestrun.Otherwiseareorfailurewilloccur.
C A U T I O N
Transporttheproductsasclosetotheinstallationlocationaspracticalbeforeunpacking.
HangingMethod
When hanging the unit ensure the balance of the unit check safety and lift it up smoothly. Do not remove any packing ma-
terials and hang the unit under packing condition with two ropes as shown below.
RAS-(2-3)HVNP1(E) RAS-(4-6)H(V)NP1E
RAS-3HVNC1 RAS-(8-10)HN(P/C)E
RAS-(4-6)H(V)NC1E RAS-12HN(P/C)
1
A
B
C
D
1
A
B
C
1. Wire rope.
A. Over 60º.
B. 0.7 to 1.0 m.
C. Do not remove the plastic band or the corrugate paper frame.
D. Pass the wire ropes through each lifting hole in the wooden base as shown.
C A U T I O N
• Lifttheoutdoorunitinitsfactorypackagingwith2wireropes.
• Forsafetyreasonsensurethattheoutdoorunitisliftedsmoothlyanddoesnotlean.
• Donotattachliftingequipmenttotheplasticbandorthecorrugatedpaperframebecauseoftheropeswillsliporbreak
thematerials.
• Ensurethattheexterioroftheunitisadequatelyprotectedwithclothorpaper.
Grossweight
Premiumseries
Model Weight(kg)
RAS-(2-2.5)HVNP1 46
RAS-3HVNP1E 77
RAS-(4-6)H(V)NP1E 116
RAS-8HNPE 149
RAS-10HNPE 151
RAS-12HNP 179
Standardseries
Model Weight(kg)
RAS-3HVNC1 49
RAS-4H(V)NC1E 85
RAS-(5-6)H(V)NC1E 95
RAS-8HNCE 149
RAS-10HNCE 151
RAS-12HNC 179