11 Electrical checks of
main parts
468
SMGB0087 rev.0 - 12/2013
11.7 Reactor (DCL)
11.7.1 Reactor (DCL) for 3N~ (400V/50Hz)
This part is used for changing the alternative current to the direct current for the inverter.
Items Specications
Character 1.0 mH+10 (at 1 kHz)
Rated current 30 A
Direct resistance 22.8 mΩ+20 (at 20 °C)
Permissible temperature range -20 ºC to 60 ºC
(mm)
11.7.2 Reactor (DCL) for 1~ (230V/50Hz)
This part is used for changing the alternative current to the direct current for the inverter.
Items Specications
Character 0.5 mH±15 (at 1 kHz)
Rated current 30 A
DC Resistance 26 mΩ (at 20 ºC)
Permissible temperature range -20ºC to 60ºC
100
(mm)