3 Piping work and
refrigerant charge
69
SMGB0087 rev.0 - 12/2013
3
For the rear side piping
After removing the rear-side piping cover, punch out the “A” holes along the guide line.
Rear Cover
N O T E
Removetherearpipecoverundertherearcoverandremove partfollowingtheslit.
2 Mount the piping cover in order to avoid water entering into the unit. Seal the holes where pipes and wires are inserted,
by using insulation (eld-supplied).
3 If the eld-supplied piping is connected with stop valves directly, it is recommended to use a tube bender.
4 Check to ensure that the stop valves are completely closed before connecting pipes.
5 Connect the eld supplied refrigerant pipes to the indoor unit and outdoor unit. Apply the oil thinly at the seat are nut
and pipe before tightening.
The required tightening torque is as follows:
PipeSize TighteningTorque(Nm)
Ø 6.35 mm (1/4) 20
Ø 9.52 mm (3/8) 40
Ø 12.70 mm (1/2) 60
Ø 15.88 mm (5/8) 80
Ø 19.05 mm (3/4) 100
6 After connecting the refrigerant piping, seal the open space between knockout hole and refrigerant pipes by using
insulation material.
Unit Side
Nº Description
Insulation Material
Insulation Material
Field Supplied
Insulation Material
7 Operation of stop valve should be performed according to the “3.2.3Outdoorunitstopvalve”explanation.