3 Piping work and
refrigerant charge
73
SMGB0087 rev.0 - 12/2013
3
Maximum refrigerant piping length
IVX Premium series
(m)
OutdoorUnit 2HP 2.5HP 3HP 4HP 5HP 6HP 8HP 10HP 12HP
Maximumpipinglength
betweentheoutdoorunit
andthefarthestindoor
unit
ActualLength(L) 50 75 100
EquivalentLength(EL) 70 95 125
Totalpipinglength
2units(A+B+C) 50 60 85 100 115
3units(A+B+C+D) -- 60 95 100 130
4units(A+B+C+D+E+F) -- 95 100 145
Maximumpipinglineafter
rstbranch
4and3units(B+C+D) 10 15
4units(B+D,B+E,C+F,
C+G)
-- 10 15
MainpipinglengthA A > B, C, D, E, F, G
MaximumheightdifferenceOutdoor/Indoor(H)
(OutdoorUnitisHigher/Lower.)
30 / 20
MaximumheightdifferenceIndoor/Indoor 3 10
Maximumheightdifference:
branchpipe/Indoor(2,3and4indoorunitssystem)
branchpipe/branchpipe(4indoorunitssystem)
3
Maximumlengthdifferenceoftheseveralbranches:
(B-C)(2and3unitsystem)
(B-D)(3unitsystem)
(C-D)(3unitsystem)
(C+G)-(C+F)(4unitsystem)
(B+E)-(B+D)(4unitsystem)
(C+G)-(B+E)(4unitsystem)
(C+G)-(B+D)(4unitsystem)
(C+F)-(B+E)(4unitsystem)
(C+F)-(B+D)(4unitsystem)
< 8