158
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
Notes:
●
The Demand Current Control (%) is value criterion. The value used for this control is calculated from the current, and
therefore it is different from the value indicated by a wattmeter. If it is required that the maximum power consumption is
managed precisely, a eld-supplied demand controller should be used.
●
The actual value may temporarily be higher than the indicated value (by 40% to100%) depending on the operating control
conditions such as protection control.
Parts Specications Remarks
Auxiliary Relay (X1, X2)
Mini-Power Relay, (Model: MY1F or MY2F)
made by OMRON
220V
Change-Over Switch (SS2, SS3) Manual Switch 220V
3 Pin Connector Cord
Model: PCC-1A
(Connected to JST Connector, XARP-3)
Five Cords with Connectors as One Set
Electric Wiring
(Inside of Unit)
Low Volt. AWG22 Lower than 24V
220V AWG18-20 /
Electric Wiring
(Outside of Unit)
Low Volt. AWG18-20 Lower than 24V
220V AWG14 /
Notes:
●
Make the wiring to the terminals as short as possible.
●
Do not run the wirings too closely to the high voltage cable. Keep at least 30cm distance between the wiring and the high
voltage cable. (Crossing cables is okay.) If it is necessary to run the wirings closer than 30cm to the high voltage cable,
insert the low voltage cable(s) in a metal tube and ground it at one end. If sealed wirings are used at the low voltage wiring
side, ground it at one end of the shielded wirings.
●
The maximum length should be within 70m.