4 Electrical Wiring
91
SMGB0064 rev.0 - 08/2011
4
DSW2: Piping length/selection function
Function Setting position
Setting before shipment
Piping length
5 m < Lt
Lt > 30 m
5 m < Lt < 30 m
Cancellation of outdoor hot start control.
(Not recommended, only available for special testing cases )
RAS-(2/6)HVRN(1)(S)(E)
Cancellation of outdoor air temperature control.
Optional function selection setting (set by PSW)
ON: set
OFF: no set
External input/output selection signals (set by PSW)
ON: set
OFF: no set
C A U T I O N
• The cancellation of the outdoor hot start control conguration could damage the compressor if it is usually
used. In that case the unit warranty will be void.
DSW3: Capacity setting
Unit Setting position Unit Setting position Unit Setting position Unit Setting position
RAS-2HVRN2
RAS-4HVRNS2E RAS-4HRNS2E RAS-8HRNSE
RAS-2.5HVRN2 RAS-5HVRNS2E RAS-5HRNS2E RAS-10HRNSE
RAS-3HVRNS2 RAS-6HVRNS2E RAS-6HRNS2E — —
DSW4 / RSW1: Refrigerant cycle setting
In case of using an H-Link II net it is required to set the refrigerant cycle number.
Setting position
(DSW4)
Setting position (RSW1)
Setting for tens
(second digit)
Setting for units
(rst digit)
Example for 16 and
Rotary switches positions (RSW1) are set by inserting a screw driver into the groove.