5 Control System
156
SMGB0064 rev.0 - 08/2011
N O T E
This sequence is for the standard operation.
*1) Fan step at start
Outdoor temp. (Tao) Air ow ratio
Tao ≤ 2 °C 15%
2 °C < Tao ≤ 12 °C 25%
12 °C < Tao ≤ 22 °C 40%
22 °C < Tao ≤ 27 °C 60%
27 °C < Tao ≤ 32 °C 80%
32 °C < Tao ≤ 37 °C 100%
37 °C < Tao 110%
*2) Temp. diference ±5 °C