7 Test Run
192
SMGB0064 rev.0 - 08/2011
Nominal value (MPa) RCI RCD RPC RPI RPK RPF(I)
Cooling
2 HP
Pd 2.73 2.88 2.85 2.89 2.84 2.78
Ps 0.88 0.78 0.82 0.80 0.81 0.80
Heating
Pd 2.37 2.83 2.51 2.65 2.68 2.54
Ps 0.66 0.67 0.67 0.67 0.67 0.67
Cooling
2.5 HP
Pd 2.79 2.91 2.90 2.93 2.95 2.88
Ps 0.87 0.81 0.84 0.81 0.78 0.78
Heating
Pd 2.37 2.53 2.35 2.50 2.72 2.58
Ps 0.66 0.66 0.66 0.66 0.66 0.66
Cooling
3 HP
Pd 2.79 3.13 2.98 2.98 2.95 —
Ps 0.99 0.78 0.78 0.80 0.81 —
Heating
Pd 2.20 2.68 2.61 2.80 2.67 —
Ps 0.66 0.63 0.63 0.63 0.63 —
Cooling
4 HP
Pd 2.83 2.91 2.92 2.92 2.91 —
Ps 0.88 0.82 0.77 0.79 2 —
Heating
Pd 2.32 2.68 2.86 2.73 3.11 —
Ps 0.65 0.68 0.64 0.63 0.64 —
Cooling
5 HP
Pd 2.87 2.90 2.91 2.92 — —
Ps 0.88 0.82 0.77 0.79 — —
Heating
Pd 2.50 2.84 2.63 2.37 — —
Ps 0.65 0.66 0.66 0.66 — —
Cooling
6 HP
Pd 2.95 — 3.00 2.99 — —
Ps 0.77 — 0.73 0.79 — —
Heating
Pd 2.65 — 2.71 2.38 — —
Ps 0.65 — 0.65 0.65 — —
Cooling
8 HP
Pd 2.93 2.97 2.97 2.98 2.97 —
Ps 0.87 0.82 0.77 0.79 0.71 —
Heating
Pd 2.31 2.68 2.86 2.73 3.21 —
Ps 0.65 0.62 0.63 0.63 0.63 —
Cooling
10 HP
Pd 2.95 2.98 3.01 3.00 — —
Ps 0.82 0.79 0.76 0.81 — —
Heating
Pd 2.47 2.54 3.00 2.35 — —
Ps 0.65 0.65 0.65 0.65 — —