8 Troubleshooting
318
SMGB0064 rev.0 - 08/2011
b. By touching the - side of the tester to the + terminal of diode
module and the + side of tester to the ~ terminals (3 NOs.) of the
diode module, measure the resistance.
If all the resistances are greater than 500kΩ, it is normal.
c. By touching the - side of the tester to the - terminal of diode
module and the + side of tester to the ~ terminals (3 NOs.) of the
diode module, measure the resistance.
If all the resistances are from 5 to 50kΩ, it is normal.