EasyManua.ls Logo

Hitachi RAS-(4-6)HVRNS2E - Opening Electrical Box (P-Mounting Plate); Removing Reversing Valve Coil

Hitachi RAS-(4-6)HVRNS2E
488 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10 Servicing
367
SMGB0064 rev.0 - 08/2011
10
Fixation of the compressor to the bottom plate
Compressor position 1 2 3 4
Vibration-proof rubber 1 x x x x
Vibration-proof rubber 2 x x
Nut x x
Opening electrical box (P-mounting plate)
1 Remove the service cover according to the section Removing service cover, see on page 361 in this chapter.
2 Remove the six (6) screws xing the electrical box. Open the P-mounting plate by rotating it to the left.
1. P Plate.
2. Upper cover.
3. Screw.
4. Two (2) screws.
1
2
3
4
4
D A N G E R
Check that the LED201 (red) located on the “W” surface PCB is OFF when opening the P-mounting plate.
Do not touch the electrical components when LED201 (Red) located on the “W” surface PCB is ON in order to
avoid an electrical shock.
Removing reversing valve coil
1 Remove the service cover according to the section Removing service cover, see on page 361 in this chapter.
2 Open the P-mounting plate according to the section Opening electrical box (P-mounting plate), see on page 367 in this
chapter.
D A N G E R
Check that the LED201 (red) located on the “W” surface PCB is OFF when opening the P-mounting plate.
Do not touch the electrical components when LED201 (Red) located on the “W” surface PCB is ON in order to
avoid an electrical shock.
3 Remove the connectors on the control PCB of the electrical box.
4 Remove the reversing valve coil by removing the screw xing the coil.
1. Reversing valve coil.
2. Screw.

Table of Contents