10 Servicing
393
SMGB0064 rev.0 - 08/2011
10
Opening electrical box (P-mounting plate)
1 Remove the service cover according to the section Removing
service cover, see on page 385 in this chapter.
• Remove the six (6) screws xing the electrical box. Open
the P-mounting plate by rotating it 90 degrees to the left.
1. Upper cover.
2. P Plate.
3. Screw.
4. Two (2) screws.
5. Electrical box (view from top).
6. P-Mounting plate.
7. Opening direction of P-Mounting Plate.
1
2
3
4
5
6
7
D A N G E R
• Check that the LED201 (red) located on the “W” surface PCB is OFF when opening the P-mounting plate.
• Do not touch the electrical components when LED201 (Red) located on the “W” surface PCB is ON in order to
avoid an electrical shock.
Removing the coils for the reversing and solenoid valves (SVA1 SVA2 and SVF)
1 Remove the service cover according to the section Removing service cover, see on page 385 in this chapter.
2 Open the P-mounting plate according to the section Opening electrical box (P-mounting plate), see on page 393 in this
chapter.
1
2
3
1 2 3 4
1. Electrical box.
2. Upper cover.
3. Rear cover.
1. SVA2.
2. SVF.
3. Reversing valve coil.
4. SVA1.