11 Electrical checks of
main parts
440
SMGB0064 rev.0 - 08/2011
11.1 Inverter
11.1.1 Inverter for IVX Series
Specications of inverter
Applicable model RAS-(4-12)HRNM(2)(E) RAS-(3-6)HVRNM(2)E
Applicable power source
3 Phase 400V 50 Hz RAS-(4-6)HRNM2E
3 Phase 380-415V 50 Hz RAS-(8-12)HRNM
1 Phase. 230V 50 Hz
Input current RAS-(4-12)HRNM(2)(E) 6-25A RAS-(3-6)HVRNM(2)E 15-30A
Control Method Vector control Vector control
Range output frequency 20-115HZ 20-115HZ
Accuracy of frequency 0.01 0.01
Controlled frequency 0.01Hz at applicable frequency range 0.01Hz at applicable frequency range
Output / characteristics
Conditions:
1 Power source voltage AC380/415V
2 Non-loading (free output)
3 Ammeter type volt-meter (X1.1)
Conditions:
1 Power source voltage AC220/240V
2 Non-loading (free output)
3 Ammeter type volt-meter (X1.1)
Soft start stop 0.125–3.00 Hz/s —