12.3 Insufcient cooling performance when a long piping is applied
Question and answer for the eld work
Example 2: Insufcient cooling performance when a long piping is applied
Phenomenon Sufcient cooling was not available for an indoor unit that was located at the farthest position.
Cause
If the location of an outdoor unit is 20 meters lower than the location of the indoor units resetting of the DIP switch DSW3
is required.
However no setting was performed. Therefore the largest discharge pressure was not increased. This resulted in an in-
sufcient cooling performance for the indoor unit.
Outdoor unit
Insucient cooling
Countermeasure The setting of the DSW2 was changed.
Remarks Pay special attention to the size of liquid pipe. Refer to “piping work in TC” for details.