EasyManua.ls Logo

Hitachi RAS-(4-6)HVRNS2E - Page 48

Hitachi RAS-(4-6)HVRNS2E
488 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Unit Installation
38
SMGB0064 rev.0 - 08/2011
Air ow guide
Specications
Model AG-335A Image
Quantity 2 per unit
1
1
2
1 Mounting dimension
2 Air ow guide
Air discharge
direction
Upward (downward)
left & right
Material
Weather proof
polypropylene resin
Color Gray
Weight 1.9 kg
Accessories
Fixing screw x 4
[M5 (SUS) x 20]
Installation manual
Installation
restriction
“Wind Guard” or “Snow protection hood” is not
available to install with air ow guide. (“Guard net”
is available to be installed together.)
Attaching example of air ow guide
Attach the air ow guide to the air discharge grille with four (4) screws (supplied).
The xing holes are located at 4 positions on the grille. (Screw tightening torque 2.4 3.1 N.m)
Do not remove the air discharge grille for air ow guide installation.
C A U T I O N
If the air guide is installed without discharge grille it may cause injury due to rotating fan.
Two ow guides installation
1 Air discharge grille
2 Air ow
3 Air ow guide (see the note)
4 Outdoor Unit
5 M5 xing screw x4 (Accessories)
N O T E
Air ow direction of both air ow guides should be the
same.
1
2
2
3
3
5
5
4
Service space (In case of upward air discharge)
In case of right and left sides air discharge enough space for
air discharge is required.
The downward air discharge is also available. In such case
install the base under the unit to secure enough space for air
discharge.
In case of serial units installation air discharge should be
upward.
1 Min. 200 mm
2 Outdoor unit
3 Air ow guide
4 Passage side
1
2
3
4

Table of Contents

Related product manuals