2 Unit Installation
38
SMGB0064 rev.0 - 08/2011
Air ow guide
Specications
Model AG-335A Image
Quantity 2 per unit
1
1
2
1 Mounting dimension
2 Air ow guide
Air discharge
direction
Upward (downward)
left & right
Material
Weather proof
polypropylene resin
Color Gray
Weight 1.9 kg
Accessories
Fixing screw x 4
[M5 (SUS) x 20]
Installation manual
Installation
restriction
“Wind Guard” or “Snow protection hood” is not
available to install with air ow guide. (“Guard net”
is available to be installed together.)
Attaching example of air ow guide
• Attach the air ow guide to the air discharge grille with four (4) screws (supplied).
• The xing holes are located at 4 positions on the grille. (Screw tightening torque 2.4 3.1 N.m)
• Do not remove the air discharge grille for air ow guide installation.
C A U T I O N
• If the air guide is installed without discharge grille it may cause injury due to rotating fan.
Two ow guides installation
1 Air discharge grille
2 Air ow
3 Air ow guide (see the note)
4 Outdoor Unit
5 M5 xing screw x4 (Accessories)
N O T E
• Air ow direction of both air ow guides should be the
same.
1
2
2
3
3
5
5
4
Service space (In case of upward air discharge)
• In case of right and left sides air discharge enough space for
air discharge is required.
• The downward air discharge is also available. In such case
install the base under the unit to secure enough space for air
discharge.
• In case of serial units installation air discharge should be
upward.
1 Min. 200 mm
2 Outdoor unit
3 Air ow guide
4 Passage side
1
2
3
4