4 Electrical Wiring
82
SMGB0064 rev.0 - 08/2011
4.1 General check
D A N G E R
Before installing the electrical wiring or before performing a periodical check, turn OFF the main switch to
the indoor unit and the outdoor unit. For safety reasons, be sure that the indoor fan and the outdoor fan have
stopped.
Prevent the wires from touching the refrigerant pipes, the plate or cutting edges and the electrical components
inside the unit, to prevent them getting damaged. In worst cases, a re may occur.
Tightly secure the wires with the cord clamp inside the indoor unit.
N O T E
In case of performing a test run operation take especially care because some security features are disabled:
the units will operate during 2 hours without Thermo-OFF, and the 3-minute guard for compressor protection
will not be effective during the test.
Fix rubber bushes with an adhesive on the panel when the conduit pipes to the outdoor unit are not used.
In forced stopped compressor mode, the compressor operation is OFF.