4 Electrical Wiring
86
SMGB0064 rev.0 - 08/2011
DSW2: Piping length/selection function
Function
Setting position
RAS-(4-6)H(V)RNM2E
RAS-3HVRNM2E
RAS-(8-12)HRNM
Setting before shipment
Piping length
5 m < Lt
Lt > 30 m
5 m < Lt < 30 m
Cancellation of outdoor hot start control. (Not recommended, only available for special testing cases)
(RAS-(4-6)H(V)RNM2E: pin 3 is OFF)
Cancellation of outdoor air temperature control.
(RAS-(4-6)H(V)RNM2E: pin 4 is OFF)
Optional function selection setting (set by PSW)
External input/output selection signals (set by PSW)
C A U T I O N
The cancellation of the outdoor hot start control conguration could damage the compressor if it is usually used.
In that case the unit warranty will be void.
• DSW3: Capacity setting
Unit Setting position Unit Setting position Unit Setting position
RAS-8HRNM
RAS-3HVRNM2E — —
RAS-10HRNM
RAS-4HVRNM2E RAS-4HRNM2E
RAS-12HRNM RAS-5HVRNM2E RAS-5HRNM2E
— — RAS-6HVRNM2E RAS-6HRNM2E
DSW4 / RSW1: Refrigerant cycle setting
In case of using an H-Link II net it is required to set the refrigerant cycle number.
Setting position
(DSW4)
Setting position (RSW1)
Setting for tens
(second digit)
Setting for units
(rst digit)
Example for 16 and
Rotary switche’s positions (RSW1) are set by inserting a screw driver into the groove.