7. Test run
177
SMGB0079 rev.0 - 01/2013
7
7.5 Test run procedure from the outdoor unit side
The test run procedure from the outdoor unit side is shown below.
You can set this DIP switch while the power source is ON.
Setting of dip switch
DSW1
1 Test Run
2 COOL/HEAT
(Setting ON: Heat Operation)
3 COOL / HEAT intermediate season
4 Manual Compressor stop
D A N G E R
• DonottouchanyotherelectricalcomponentswhileyouaresettingtheswitchesonthePCB.
• DonotattachordetachtheserviceaccesspanelwhenthepowersourcefortheoutdoorunitisONandthe
outdoorunitisoperating.
• SetalltheDIPswitchesofDSW1toOFFaftercompletingthetestrun.
Operation Dip Switch Setting Operation Remarks
Test Run
Setting of Operation Mode:
Cooling: Set DSW1-2 OFF.
Heating: Set DSW1-2 ON.
Starting Test Run:
Set DSW1-1 ON and the ope-
ration is started after a few ~20
seconds.
Cooling Heating
The indoor unit automatically start to
operate when the test run of the outdoor
unit is set.
The ON/OFF operation can be per-
formed from the remote control switch or
DSW1-1 of the outdoor unit.
Continuous operation during 2 hours
is performed without Thermo-OFF.
N O T E
• TEST RUN operation time can be
increased depressing the time
switch in the Remote Control.
• If is setting DSW1-3 ON, cooling/
heating intermediate season
mode is activaded.
• Take care that the indoor units start
operation in accord with the test run
operation of the outdoor unit.
• The test run is started from the outdo-
or unit and stopped from the remote
control switch, the test run function
of the remote control switch is cance-
lled. However, the test run function of
the outdoor unit is not cancelled
• In case that the plural indoor units
are connected with one remote con-
trol switch, all the units start test run
operation at the same time, therefore,
turn the power source OFF for the in-
door units not to operate test run. In
this case, the “TEST RUN” indication
of the remote control switch may ic-
ker, and this is not abnormal.
• The setting of DSW1 is not required
for the test run from the remote con-
trol switch.
Manual
OFF of
Compressor
Setting:
Compressor Manual OFF:
Set DSW1-4 ON.
Compressor ON:
Set DSW1-4 OFF.
When DSW1-4 is ON during com-
pressor operation, the compressor stops
to operate immediately and the indoor
unit is under the condition of Thermo-
OFF.
When DSW1-4 is OFF, the com-
pressor starts to operate after the can-
cellation of 3-minutes guard.
• Do not repeat compressor ON/OFF
frequently.