EasyManua.ls Logo

Hitachi RAS-4-HNPE - Removing Electrical Box

Hitachi RAS-4-HNPE
480 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10. Servicing
411
SMGB0079 rev.0 - 01/2013
10
10.4.2.6 Removing electrical box
1  Remove the service cover following Removing service cover.
2  Remove the upper cover following Removing upper cover.
3  Remove 6 screws which x the electrical box.
4  Pull up and remove the electrical box.
Upper cover
Electrical box
Remove the
xing screws
N O T E
Thefollowingwiringmustberemovedtodismounttheelectricalbox.
1.  Removethereversingvalvecoilfromthereversingvalve.:Removingreversingvalvecoil.
2.  Removetheexpansionvalvecoilfromtheexpansionvalve.:Removingelectronicexpansionvalvecoil.
3.  Removethesolenoidvalvecoilfromthesolenoidvalve.:Removingsolenoidvalvecoil.
4.  RemovetheFastonterminalsofhighpressureswitchandthepressureswitchforcontrolfromtheswitch
body:Removingthehighpressureswitchandpressureswitchforcontrol.
5.  RemoveallconnectorsonthecontrolPCB.
6.  Removethecompressorwiresintheterminalboxofthecompressor.
7.  Toremounttheelectricalboxattachtheelectricalboxttingwiththepartitionplate.
(InserttheradiationnintotheU-notchonthepartitionplateandplacethenonthefanboxside.Then
attachtheelectricalboxhookingontothepartitionplate).
Front
Side
Original Position
Front
side
Original position
Partition Plate
Front
Side
Electrical Box (Radiation Fin)
Set the electrical box (radiation fin)
in front of the partition plate.
(Refer to the above picture “Original Position”.)
Front
side
Partition plate
Place the electrical box (radiation n) in
front of the partition plate.
(Refer to the original position)
Electrical box (radiation n)
Front
side
Place the electrical box to hook the parts
onto the partition plate.