89
Alarm
Code
24
Abnormality of Thermistor for Evaporating Temperature
during Heating Operation (Outdoor Unit Evaporating Thermistor)
●
The alarm code is ashed on the 7-segment display of the outdoor unit.
●
The alarm code is displayed on the wired controller of the indoor unit.
★
This alarm code is displayed when a short circuit (0.2kΩ or less) or disconnection (500kΩ or more) of
the thermistor is detected during heating or cooling operation.
TROUBLESHOOTING