DSW4: Refrigerant Cycle Number setting
Setting is required
Setting before shipment
(Setting for the ten digit)
DSW5: End terminal resistance
No setting is required
Setting before shipment
DSW6: Height difference
Setting is required
Setting before shipment
The indoor unit is located higher than outdoor
unit (20 to 30 m)
Fine-tuning of heating capacity
10.5.2 PCB2
DSW1: (On PCB2)
No setting is required
When set Nº1 pin to ON, the electric current
detection is canceled. Nº 1 pin should be set
back to OFF after electrical work.
JP1~6: Jumper cable
JP1 With jumper cable JP4 Without jumper cable
JP2 With jumper cable JP5 With jumper cable
JP3 Without jumper cable JP6 With jumper cable
! CAUTION
Ifthepowersourceisopenphase,"05"willbedisplayedat7-segmenton
theoutdoorPCB,andthecompressorwillnotbeoperated.Inthiscase
checkfortheconnectionofpowersourceterminal.
11 COMMISSIONING
When installation is completed, perform test run according to the
following procedure, and hand over the system to the customer.
Perform test run regarding indoor units one by one in order, and
conrm that the electrical wiring and the refrigerant piping are
correctly connected.
Start the indoor units one by one in order to conrm that they
are correctly numbered.
! CAUTION
• Do not operate the system until all the check points have been
cleared.
aChecktoensurethattherefrigerantpipingandtransmission
betweenoutdoorunitandindoorunitsareconnectedtothesame
refrigerantcycle.Ifnot,itwillcauseanabnormaloperationanda
seriousaccident.
bChecktoensurethattheelectricalresistanceismorethan1
megohm,bymeasuringtheresistancebetweengroundandthe
terminaloftheelectricalparts.Ifnot,donotoperatethesystem
untiltheelectricalleakageisfoundandrepaired.
cChecktoensurethatthestopvalvesoftheoutdoorunitarefully
opened,andthenstartthesystem.
dChecktoensurethattheswitchonthemainpowersourcehas
beenONformorethan12hours,towarmthecompressoroilby
theoilheater.
eCheckthattherefrigerantpipingandtheelectricalwiring
conformtothesamesystem,andcheckthatthedipswitchsetting
oftherefrigerantcycleNº.(DSW4&RSW1[O.U.],DSW5&
RSW2[I.U.])andtheunitnumber(RSW)fortheindoorunitsapply
tothesystem.
Conrmthatthedipswitchsettingontheprintedcircuitboardof
theindoorunitsandtheoutdoorunitsarecorrect.Especially,pay
attentiontothesettingofliftbetweenindoorunitsandoutdoor
unit,therefrigerantNo.andtheendterminalresistance.
f Checktoensurethattheelectricalresistanceismorethan1
megohm,bymeasuringtheresistancebetweengroundandthe
terminaloftheelectricalparts.Ifnot,donotoperatethesystem
untiltheelectricalleakageisfoundandrepaired.Donotapplythe
voltageontheterminalsfortransmission1and2.
gChecktoensurethateachwire,L1,L2,L3andNiscorrectly
connectedatthepowersource.
Ifincorrectlyconnected,theunitwillnotoperateandtheremote
controlswitchwillindicatethealarmcode“05”.Inthiscase,check
andchangethephaseofthepowersourceaccordingtothe
attachedseatonthereversesideoftheservicecover.
hCheckthatthegasandliquidlinestopvalvearefullyopen.
Checkthearenutsarefullyclosed.
• FSNM series outdoor units does not operate within 4 hours after
powersupply(StoppageCoded1-22).Incaseofoperatingwithin4
hours,releasetheprotectioncontrolasfollows:
1 Supplypowertotheoutdoorunitandindoorunits.
COMMISSIONING
PMML0390B REV.0 - 11/2015 - P5416649