12 MAIN SAFETY DEVICES
Compressor Protection
The compressor is protected by the following devices and their combinations.
• High Pressure Switch: This switch cuts out the operation of the compressor when the discharge pressure exceeds the setting.
Oil Heater: This band type heater protects against oil foaming during cold starting, as it is energized while the compressor is
stopped.
AC Fan Motor Protection
Internal thermostat: Embedded in the fan motor winding, this internal thermostat cuts out the operation of the fan motor when the fan
motor winding temperature exceeds the setting.
Safety and control device setting for outdoor units
Model RAS-8FSNM RAS-10FSNM RAS-12FSNM
For compressor Automatic Reset, Non-Adjustable
Pressure switch (each one for each compressor)
High Cut-out MPa 4.15
-0.05
4.15
-0.05
4.15
-0.05
-0.15 -0.15 -0.15
Cut-in MPa 3.20±0.15 3.20±0.15 3.20 ±0.15
Fuse capacity
A 40 40 40
3N~ 400V 50Hz
CCP timer Non-Adjustable
Setting time min. 3 3 3
For condenser AC fan motor Automatic Reset, Non-Adjustable
Internal thermostat (each one for each motor)
DC Cut-out ºC 125±5 125±5 125±5
AC Cut-out ºC 150±5 150±5 150±5
Cut-in ºC 150±5 150±5 150±5
For control circuit
Fuse capacity PCB1,5 A 5 5 5
Fuse capacity PCB3 A 10 10 10
CCPTimer:Enforced3minutesoperationandstoppage.
MAIN SAFETY DEVICES
PMML0390B REV.0 - 11/2015 - P5416649