Dehumidifying Sleep Operation
Notes:
(1) The sleep operation starts when the sleep key is pressed.
(2) When the sleep key is set, the indoor fan is set to “sleep silent” (FDOY_M or AFDOY).
(3) The indoor fan speed does not change even when the fan speed mode is changed.
(4) If the set time is changed during sleep operation, all data including set temperature, time, etc. is cleared and
restarted.
(5) If sleep operation is canceled by the cancel key or sleep key, all data is cleared.
(6) If the position of air deflector is being operated using remote control, the operation will be performed at any
desired position of air deflector.
Dehumidifying
Notes:
(1) If the room temperature is (cooling preset temperature) - (1.33°C) or less after 30 seconds from starting the operation, the operation is done assuming as the preset
temperature = (room temperature at the time) - (2°C).
(2) The indoor fan is operated in the “Lo” mode. During thermo OFF indoor fan will be OFF for 5 minutes and ON for 1 minute.
(3) When the operation is started by the themostat turning ON, the start of the indoor fan is delayed 32 seconds after the start of compressor operation.
(4) The compressor is operated forcedly for 3 minutes after operation is started.
(5) The minimum ON time and OFF time of the compressor are 3 minutes.