[No operation or abnormal operation]
Is AC220-240V being
supplied to terminal L and
N? Be sure terminal L, N
and A, B are properly
connected.
Is the 25A fuse normal?
If the 25A fuse has blown, be aware
that other parts may also be defective
(mainly, varistor 2, diode stack,
smoothing capacitors, system power
module, etc.).
No
Ye s
CHECKING THE OUTDOOR UNIT ELECTRICAL PARTS
Replace any defective parts.
Is the power circuit normal?
See the description on
power circuit for details.
Is 5V being generated
between Pin 4 (0V) and pin
3 (5V) at CN 19 (test pin)?
Operate the outdoor unit
according to the instruction
How to operate the outdoor
unit independently
.
How did the self-diagnosis
lamp (LD301) light?
Is the switching power circuit OK?
Has the 5A fuse blown?
See the self-diagnosis lamp
lighting mode.
Check to see whether the
connected C and D cable
correctly? If reversed, correct the
cable connection.
Replace any defective parts.
If the 5A fuse has blown, the
switching transformer (T1),
varistor 2, R716, etc. may
also be defective.
()
No
Ye s
Ye s
No
Ye s