10.14 Removing the liquid pipe thermistor
D A N G E R
• Turn OFF all the power source switches.
1 Remove the front service cover as described in the procedure Removing the front service cover, see on page 292.
2 Remove
the
cover of the electrical box as described in the procedures Removing the electrical box for RAS-
(8-12)FSXN, see on page 295 and Removing the electrical box for RAS-(14-18)FSXN, see on page 295.
3 Remove the cork tape -E- and pull out the thermistor -G- with the fixing plate -I- from the pipe -F-.
4 Remove the thermistor from the fixing plate -I-.
N O T E
When removing
the thermistor of the liquid pipe, take care not to catch your hands or the thermistor on the
valve stay of the stop valve.
5 To fit the thermistor, carry out this procedure in reverse order.
N O T E
• When fitting
the thermistor, fix it with the end of the vinyl pipe -H- downward, to avoid entering water into
the pipe -F-.
• Seal again the whole circumference of the pipe -F- with the cork tape -E-.
N O T E
The above procedure should be used to remove the other thermistors (Te, Tbg, Tg and Tchg).
•
Position of the thermistor in the RAS-12FSXN unit.
10 Servicing
320
SMGB0065 rev. 1 - 12/2010