EasyManua.ls Logo

Hitachi RCI - Automatic Cooling;Heating Operation Control; Preventive High-Pressure Increase Control

Hitachi RCI
408 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.3.4 Automatic cooling/heating operation control
5.3.5 Preventive high-pressure increase control
This function is used to avoid an abnormal condition (alarm: 02) when the outdoor air flow drops due to seasonal winds
blowing against the air outlet. When CMC is enabled in cooling operation, PSC is enabled and Tc is greater than Tc1+4 °C,
operations with forced thermostat disabling are started.
Tc: Outdoor pipe temperature.
Tc1: Outdoor pipe temperature when the PSC is enabled.
PSC enabled: 3.60 MPa.
However, if this occurs more than 6 times during operations, thermostat stoppage is not forced. The cause of the stoppage
will be 13.
5 Control system
179
SMGB0063 rev. 1 - 10/2010
5

Table of Contents

Related product manuals