EasyManua.ls Logo

Hitachi RPI-1.5FSRE - 4.4 SERVICE AND OPERATION SPACE FOR RPI-(1.5~2.0)FSRE

Hitachi RPI-1.5FSRE
450 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.4 SERVICE AND OPERATION SPACE FOR RPI-(1.5~2.0)FSRE
This unit o󰀨ers the exibility to mount the electrical box in di󰀨erent congurations to suit the space available on each occasion.
? NOTE
A service access from the bottom side is required for servicing and maintenance.
4.4.1 Service space for electrical box on left
side conguration
a
b c d
e
e
f
Electrical
box
Top view
Service space (mm)
a b c d e f
800 300 750 100 1000 657
4.4.2 Service space for electrical box on right
side conguration
Top view
a
b c d
e
e
f
Electrical
box
Service space (mm)
a b c d e f
657 200 750 300 1000 800
4.4.3 Service space for wall mounted electrical
box conguration
Top view
a b c
d
d
e
Electrical Box
Service space (mm)
a b c d e
200 750 100 1000 657
4.4.4 Service space for lower extraction of the
air lter
a
b
Service space (mm)
a b
700 200
INDOOR UNITS INSTALLATION
PMML0528 rev.1 - 02/2021
9