4-21
Chapter 4
For parameter configuration
[AH-85] to [AH-96]
PID sleep function
Code/Name
Range (unit)
Initial
value
AH-85
PID sleep trigger selection
00(Disable)/
01(Low output)/
02([SLEP] terminal)
00
AH-86 PID sleep start level
0.00 to 590.00(Hz)
0.00
AH-87 PID sleep active time
0.00 to 100.00(s)
0.00
AH-88 Enable set-point boost
before PID sleep
00(Disable)/
01(Enable)
00
AH-89 Set-point boost time
before PID sleep
0.00 to 100.00(s)
0.00
AH-90 Set-point boost value
before PID sleep
0.00 to 100.00(%)
0.00
AH-91 Minimum RUN time
before PID sleep
0.00 to 100.00(s)
0.00
AH-92 Minimum active time
of PID sleep
0.00 to 100.00(s)
0.00
AH-93 PID wake trigger
selection
01(Deviation)/
02(Low feedback)/
03([WAKE] terminal)
01
AH-94
PID wake start level
0.00 to 100.00(%)
0.00
AH-95
PID wake start time
0.00 to 100.00(s)
0.00
AH-96 PID wake start
deviation value
0.00 to 100.00(%)
0.00
The PID sleep function temporally reduces the PID
output, achieving an energy saving state.
If [AH-88]"Enable set-point boost before PID sleep" is
enable, during [AH-89] setting time before PID sleep,
the [AH-90] boost amount is added to the PID target
value to increase the feedback amount.
As a result, it is possible to maintain sleep for a longer
time.
Operation example of the sleep function.
Example 1) [AH-85]=01(Low output)
[AH-93]=01(deviation)
Example 2) [AH-85]=01(Low output)
[AH-93]=02(Low feedback)
Example 3) [AH-85]=02(output terminal 058[SLEP])
[AH-93]=03(output terminal 059[WAKE])
There are 4 independent PID control blocks in P1.
By switching the input terminal 056[PIO1]/057[PIO2],
PID1 to PID4 can be switched.
Combination of [PIO1]/[PIO2]
057[PIO2]
056[PIO1]
PID1 is enabled
OFF
OFF
PID2 is enabled
OFF
ON
PID3 is enabled
ON
OFF
PID4 is enabled
ON
ON
Feedback value
PID Target value
Output frequency
Terminal [SLEP]
Terminal [WAKE]
ON
ON
[AH-87]
[AH-95]
PID Target value
[AH-94]
[AH-86]
Output frequency
[AH-95]
Feedback value
[AH-87]
PID Target value
[AH-94]
[AH-86]
Output frequency
[AH-95]
Feedback value
[AH-87]
PID
Output
command
PID1 control
PID2 control
PID output
switch
[PIO1]/[PIO2]
[db-50]
PID3 control
PID4 control
[db-55]
[db-57]
[db-59]