Chapter 8 List of Data Settings
8-11
Monitored data or setting
Change during
RUN operation
Levels and output terminal status
Low-current indication signal
output mode selection
00 (output during acceleration/deceleration and constant-speed
operation), 01 (output only during constant-speed operation)
Low-current indication signal
detection level
0.00 to 2.00 x "rated current" (A)
<0.00 to 1.80 x "rated current" (A) > (In case of CT)
0.00 to 1.50 x "rated current" (A) (In case of VT)
Overload signal output mode
00 (output during acceleration/deceleration and constant-speed
operation), 01 (output only during constant-speed operation)
0.00 to 2.00 x "rated current" (A)
<0.00 to 1.80 x "rated current" (A) > (In case of CT)
0.00 to 1.50 x "rated current" (A) (In case of VT)
Frequency arrival setting for accel.
0.00 to 99.99, 100.0 to 400.0 (Hz)
Frequency arrival setting for decel.
0.00 to 99.99, 100.0 to 400.0 (Hz)
PID deviation level setting
Frequency arrival setting for
acceleration (2)
0.00 to 99.99, 100.0 to 400.0 (Hz)
Frequency arrival setting for
deceleration (2)
0.00 to 99.99, 100.0 to 400.0 (Hz)
Maximum PID feedback data
Minimum PID feedback data
Over-torque (forward-driving) level
setting
0. to 200. (%) <0. to 180. (%)>
Over-torque (reverse regenerating)
level setting
0. to 200. (%) <0. to 180. (%)>
Over-torque (reverse driving) level
setting
0. to 200. (%) <0. to 180. (%)>
Over-torque (forward
regenerating) level setting
0. to 200. (%) <0. to 180. (%)>
Electronic thermal warning level
setting
00 (disabling), 01 (3 bits), 02 (4 bits)
Zero speed detection level
0.00 to 99.99, 100.0 (Hz)
Heat sink overheat warning level
Communication speed selection
02 (loopback test), 03(2400bps), 04(4800bps),
05(9600bps), 06(19.2kbps), 07(38.4kbps),
08(57.6kbps), 09(76.8kbps), 10(115.2kbps)
Communication data length
selection
Communication parity selection
00 (no parity), 01 (even parity), 02 (odd parity)
Communication stop bit selection
Selection of the operation after
communication error
00 (tripping), 01 (tripping after decelerating and stopping the
motor), 02 (ignoring errors), 03 (stopping the motor after
free-running), 04 (decelerating and stopping the motor)
Communication timeout limit
before tripping
Communication mode selection
00(ASCII), 01(Modbus-RTU)
[O] input span calibration
0. to 9999., 1000 to 6553(10000 to 65530)
[OI] input span calibration
[O2] input span calibration
(Do not change this parameter, which is intended for factory
adjustment.)
Up/Down memory mode selection
00 (not storing the frequency data), 01 (storing the frequency data)
00 (resetting the trip when RS is on),
01 (resetting the trip when RS is off),
02 (enabling resetting only upon tripping [resetting when RS is
on]), 03(resetting only trip)
00 (starting with 0 Hz), 01 (starting with matching frequency),
02 (restarting with active matching frequency)
(Note) < >indicate the setting range of 75 to 150kW
(Note) CT : Constant torque mode, VT : variable torque mode, you can set CT or VT by b049.