B−36
Parameter group B
Register
No.
Function name Function code R/W Monitoring and setting items
Data
resolution
1301h
Restart mode on power
failure / under-voltage trip
b001 R/W
0 (tripping), 1 (starting with 0 Hz), 2 (starting
with matching frequency), 3 (tripping after
deceleration and stopping with matching
frequency), 4 (restarting with active matching
frequency)
-
1302h
Allowable unde
-voltage
power failure time
b002 R/W 3 to 250 0.1 [sec.]
1303h
Retry wait time before
motor restart
b003 R/W 3 to 1000 0.1 [sec.]
1304h
Instantaneous power
failure/under-voltage trip
alarm enable
b004 R/W
0 (disabling), 1 (enabling), 2 (disabling during
stopping and decelerating to stop)
-
1305h
Number of restarts on
power failure/under-voltage
trip events
b005 R/W 0 (16 times), 1 (unlimited) -
1306h
(Reserved) - - -
-
1307h
Restart frequency threshold
b007 (high) R/W
0 to 40000
0.01 [Hz]
1308h b007 (low) R/W
1309h
Restart mode on over
voltage / over current
b008 R/W
0 (tripping), 1 (starting with 0 Hz), 2 (starting
with matching frequency), 3 (tripping after
deceleration and stopping with matching
frequency), 4 (restarting with active matching
frequency)
-
130Ah
(Reserved) - - -
-
130Bh
Number of retry on over
voltage / over current
b010 R/W 1 to 3 1 [time]
130Ch
Retry wait time on over
voltage / over current
b011 R/W 3 to 1000 0.1 [sec.]
130Dh Level of electronic thermal b012 R/W 200 to 1000 0.1 [%]
130Eh
Electronic thermal
characteristic
b013 R/W
0 (reduced-torque characteristic), 1
(constant-torque characteristic), 2 (free
setting)
-
130Fh (Reserved) - - Inaccessible -
1310h
Free setting, electronic
thermal frequency (1)
b015 R/W 0 to 400 1 [Hz]
1311h
Free setting, electronic
thermal current (1)
b016 R/W 0 to Rated current 0.1 [A]
1312h
Free setting, electronic
thermal frequency (2)
b017 R/W 0 to 400 1 [Hz]
1313h
Free setting, electronic
thermal current (2)
b018 R/W 0 to Rated current 0.1 [A]
1314h
Free setting, electronic
thermal frequency (3)
b019 R/W 0 to 400 1 [Hz]
1315h
Free setting, electronic
thermal current (3)
b020 R/W 0 to Rated current 0.1 [A]
1316h
Overload restriction
operation mode
b021 R/W
0 (disabling), 1 (enabling during acceleration
and constant-speed operation), 2 (enabling
during constant-speed operation), 3 (enabling
during acceleration and constant-speed
operation [speed increase at regeneration])
-
1317h Overload restriction level b022 R/W 200 to 2000 0.1 [%]
1318h
Deceleration rate at
overload restriction
b023 R/W 1 to 30000 0.1 [sec.]
1319h
Overload restriction
operation mode (2)
b024 R/W
0 (disabling), 1 (enabling during acceleration
and constant-speed operation), 2 (enabling
during constant-speed operation), 3 (enabling
during acceleration and constant-speed
operation [speed increase at regeneration])
-
131Ah Overload restriction level 2 b025 R/W 200 to 2000 0.1 [%]
131Bh
Deceleration rate at
overload restriction (2)
b026 R/W 1 to 30000 0.1 [sec.]
131Ch
Overcurrent suppression
enable
b027 R/W 0 (disabling), 1 (enabling) -
131Dh
Current level of active freq.
matching
b028 R/W 100 to 2000 0.1 [%]
131Eh
Deceleration rate of active
freq. matching
b029 R/W 1 to 30000 0.1 [sec.]