B−37
Register
No.
Function name Function code R/W Monitoring and setting items
Data
resolution
131Fh
Start freq. of active
frequency matching
b030 R/W
0 (frequency at the last shutoff), 1 (maximum
frequency), 2 (set frequency)
-
1320h
Software lock mode
selection
b031 R/W
0 (disabling change of data other than "b031"
when SFT is on), 1 (disabling change of data
other than "b031" and frequency settings
when SFT is on), 2 (disabling change of data
other than "b031"), 3 (disabling change of data
other than "b031" and frequency settings), 10
(enabling data changes during operation)
-
1321h (Reserved) - - - -
1322h
Motor cable length
parameter
b033
R/W
5 to 20 -
1323h
Run/power-on warning time
b034 (high) R/W
0 to 65535 1 [10h]
1324h b034 (low) R/W
1325h
Rotation direction
restriction
b035 R/W
0( Enable for both dir)/ 1 (Enable for
forward only)/ 2 (Enable for reverse only)
-
1326h
Reduced voltage start
selection
b036 R/W
0 (minimum reduced voltage start time) to 255
(maximum reduced voltage start time)
-
1327h
Function code display
restriction
b037 R/W
0 (full display), 1 (function-specific display), 2
(user setting), 3 (data comparison display), 4
(basicdisplay), 5(monitor display)
-
1328h Initial displa
selection b038 R/W 001-060 -
1329h
Automatic use
parameter
registration
b039 R/W 0 (disabling), 1 (enabling) -
132Ah Torque limit selection b040 R/W
00 (quadrant-specific setting), 01 (switching by
terminal), 02 (analog input)
-
132Bh
Torque limit 1 (fwd-powe
in
4-quadrant mode)
b041 R/W 0 to 200/255 (no) 1 [%]
132Ch
Torque limit 2 (rev
egen. in
4-quadrant mode)
b042 R/W 0 to 200/255 (no) 1 [%]
132Dh
Torque limit 3 (rev
in
4-quadrant mode)
b043 R/W 0 to 200/255 (no) 1 [%]
132Eh
Torque limit 4 (fwd/regen. in
4-quadrant mode)
b044 R/W 0 to 200/255 (no) 1 [%]
132Fh
Torque limit LADSTOP
enable
b045 R/W 0 (disabling), 1 (enabling) -
1330h
Reverse Run protection
enable
b046 R/W 0 (disabling), 1 (enabling) -
1331h to
1332h
(Reserved) - - - -
1333h Dual Rating Selection b049 R/W 0(CT mode)/1(VT mode)
-
1334h
Controlled deceleration on
power loss
b050 R/W
0 (disabling), 1 (enabling), 2, (nonstop
operation at momentary power failure (no
restoration))
3, (nonstop operation at momentary power
failure (restoration to be done))
-
1335h
DC bus voltage trigger level
of ctrl. decel.
b051 R/W 0 to 10000 0.1 [V]
1336h
Ove
-voltage threshold of
ctrl. decel.
b052 R/W 0 to 10000 0.1 [V]
1337h
Deceleration time of ctrl.
decel.
b053 (high) R/W
0.01 to 36000
0.01
[sec.]
1338h b053 (low) R/W
1339h
Initial freq. drop of ctrl.
decel.
b054 R/W 0 to 1000 0.01 [Hz]
133Ah to
133Eh
(Reserved) - - - -
133Fh
Maximum-limit level of
window comparators O
b060 R/W
0. to 100. (lower limit : b061 + b062 *2) (%)
1 [%]
1340h
Minimum-limit level of
window comparators O
b061 R/W
0. to 100. (lower limit : b060 - b062*2) (%)
1 [%]
1341h
Hysteresis width of window
comparators O
b062 R/W
0. to 10. (lower limit : b061 - b062 / 2) (%)
1 [%]
1342h
Maximum-limit level of
window comparators OI
b063 R/W
0. to 100. (lower limit : b064 + b066 *2) (%)
1 [%]
1343h
Minimum-limit level of
window comparators OI
b064 R/W
0. to 100. (lower limit : b063 - b066 *2) (%)
1 [%]
1344h
Hysteresis width of window
comparators OI
b065 R/W
0. to 10. (lower limit : b063 - b064 / 2) (%)
1 [%]