EasyManua.ls Logo

Hitachi YUTAKI S80 Series - Page 145

Hitachi YUTAKI S80 Series
158 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11. Installation conguration
TCGB0075 rev.0 - 11/2012
145
11
Swimming pool combination (Installation example 8)
Two space heating applications (High & Low water temperature) + optional Domestic Hot Water Tank + Swimmping pool
combination + Heating complement (Boiler or Electric heater combination): Two space heating application with a Room
Thermostat as an option and swimming pool space heated by Heat Pump and alternating boiler or supplemented by 3-sta-
ge electrical heater. Swimming pool is connected to the main circuit through a 3-way valve (ATW-3WV-01/02 accessory)
and a heat exchanger (eld supplied). Domestic Hot Water Tank is heated by Heat Pump. The LCD is integrated with the 
DHW Tank or supplied as necessary accessory if indoor unit is alone.
N O T E
When YUTAKI S80 is working with a swimming pool the 3-way valve accessory is needed (ATW-3WV-01 or ATW-
3WV-02).
Item Description
1 Outdoor unit
2 Indoor unit
3 R134a compressor
4 Water pump
5 3-way valve
6 T-branch
7 Shut-off valves (eld supplied)
8 Domestic hot water tank
9
Security valve
(DHWT-SWG-01 accessory)
10
DHWT heater
(integrated with DHWT)
11
LCD controller
(integrated with DHWT)
Item Description
12
Second temperature kit
(ATW-2KT-01 accessory)
13 Motorized valve (eld supplied)
14
Aquastat
(ATW-AQT-01 accessory)
15 Boiler (eld supplied)
16
Water check valve
(ATW-WCV-01 accessory)
17 Solar Kit (eld supplied)
18
Solar pump & control
(eld supplied)
19 Solar panel (eld supplied)
20
Hydraulic separator
(ATW-HSK-01 accessory)
Item Description
21
Swimming pool heat exchanger 
(eld supplied)
22
3-way valve
(ATW-3WV-01/02 accessory)
A
2nd Water Temperature sensor
(ATW-WTS-02 accessory)
B Secondary water pump
C Mixing valve 
D Hydraulic separator
E Shut-off valve
F
Universal water sensor (Two3)
(ATW-WTS-02Y accessory)
G
Water pump 3 (WP3)
(eld supplied)
12
D
E
9
B
C
A
G
F
Boiler
Boiler
Signal
20
13
16
Domestic
Water
High Temperature (80ºC)
Low Temperature (35ºC)
1
7
4
6
5
3
2
DHW Tank
17
18
Solar Kit (eld supplied)
15
17
7
16
19
11
10
8
14
21
Swimming pool space (last priority)
22