EasyManua.ls Logo

Hitachi YUTAKI S80 Series - Page 44

Hitachi YUTAKI S80 Series
158 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2. Features and benets
TCGB0075 rev.0 - 11/2012
44
Three different possible water temperature set-point conguration modes for each zone
•  OTC Points: Water target is selected by an Outside Temperature Compensated (OTC) control that is dened by 4 
different points (Minimum and maximum water outlet temperature vs Minimum and maximum outdoor ambient tempe-
rature).
Outdoor ambient temperature (ºC)
(44) Tsh
n
h
(20) Tshr
n
l
Tah
n
l (-20)
Tah
n
h (20)
Water outlet temperature
set-point (ºC)
Outdoor ambient
temperature(ºC)
Temperature setting at low
ambient temperature
Temperature setting at high
ambient temperature
Low ambient
temperature
High ambient
temperature
•  OTC Gradient (Only for heating space): Water target is selected by an Outside Temperature Compensated (OTC)
control that is dened by a different gradient of the curve. The initial point of the curve is always 20ºC-20ºC (Water 
outlet target 20ºC at outdoor ambient temperature of 20ºC).
Water outlet temperature set-point (ºC)
Outdoor ambient temperature (ºC)
•  Fixed temperature: Water target value is dened by a xed temperature set by the user.  
Outdoor ambient temperature (ºC)
Water temperature
set point ºC
Tf
n
Water outlet temperature
set-point (ºC)
Outdoor ambient
temperature(ºC)
Fixed water outlet 
temperature setting

Table of Contents

Other manuals for Hitachi YUTAKI S80 Series

Related product manuals