 WIRING SIZE AND MINIMUM REQUIREMENTS OF THE PROTECTION DEVICES
C A U T I O N
&KHFN WR HQVXUH WKDW WKH ¿HOG VXSSOLHG HOHFWULFDO FRPSRQHQWV
(mains power switches, circuit breakers, wires, connectors and wire
terminals) have been properly selected according to the electrical
data indicated on this chapter and they comply with national and local
codes. If it is necessary, contact with your local authority in regards to
standards, rules, regulations, etc.
Use a dedicated power circuit for the indoor unit. Do not use a power
circuit shared with the outdoor unit or any other appliance.
N O T E
Electric fuses can be used instead of magnetic Circuit Breakers (CB).
In that case, select fuses with similar rated values as the CB.
The Earth Leakage Breaker (ELB) mentioned on this manual is also
commonly known as Residual Current Device (RCD) or Residual
Current Circuit Breaker (RCCB).
The Circuit Breakers (CB) are also known as Thermal-Magnetic
Circuit Breakers or just Magnetic Circuit Breakers (MCB).
Use wires which are not lighter than the polychloroprene
VKHDWKHGÀH[LEOHFRUGFRGHGHVLJQDWLRQ,(&
Outdoor unit
Model Power supply
Max.
current
(A)
Power supply cables
Transmitting
cables
CB
(A)
ELB
(nº of poles/A/mA)
(1 (1
RAS-4WHVNPE
1~ 230V 50Hz
20 2 x 4.0 mm² + GND
2 x 0.75 mm
2
20
2/40/30RAS-5WHVNPE 25 2 x 6.0 mm² + GND 25
RAS-6WHVNPE 25 2 x 6.0 mm² + GND 25
RAS-4WHNPE
3N~ 400V 50Hz
14 4 x 2.5 mm² + GND 15
4/40/30
RAS-5WHNPE 14 4 x 2.5 mm² + GND 15
RAS-6WHNPE 16 4 x 4.0 mm² + GND 20
Indoor unit alone
Model
Power
supply
Operation mode
Max.
current
(A)
Power supply
cables
Transmitting
cables
CB
(A)
ELB
(nº of
poles/A/
mA)
(1 (1
RWH-4.0VNFE
1~
230V
50Hz
Without simultaneous operation
of electric heater in DHW tank
24 2 x 6.0 mm² + GND
2 x 0.75 mm
2
32
2/40/30
With simultaneous operation of
electric heater in DHW tank
38 2 x 10.0 mm² + GND 40
RWH-5.0VNFE
Without simultaneous operation
of electric heater in DHW tank
28 2 x 6.0 mm² + GND 32
With simultaneous operation of
electric heater in DHW tank
42 2 x 10.0 mm² + GND 50 2/63/30
RWH-6.0VNFE
Without simultaneous operation
of electric heater in DHW tank
31 2 x 6.0 mm² + GND 32 2/40/30
With simultaneous operation of
electric heater in DHW tank
45 2 x 10.0 mm² + GND 50 2/63/30
RWH-4.0NFE
3N~
400V
50Hz
Without simultaneous operation
of electric heater in DHW tank
10 4 x 2.5 mm² + GND 15
4/40/30
With simultaneous operation of
electric heater in DHW tank
24 2 x 4.0 mm² + GND 25
RWH-5.0NFE
Without simultaneous operation
of electric heater in DHW tank
10 4 x 2.5 mm² + GND 15
With simultaneous operation of
electric heater in DHW tank
24 2 x 4.0 mm² + GND 25
RWH-6.0NFE
Without simultaneous operation
of electric heater in DHW tank
10 4 x 2.5 mm² + GND 15
With simultaneous operation of
electric heater in DHW tank
24 2 x 4.0 mm² + GND 25
N O T E
The data corresponding to DHW tank heater is calculated in combination with the YUTAKI S80 domestic hot water tank accessory “DHWT-(200/300)
S-3.0H2E”.
ELECTRICAL AND CONTROL SETTINGS
PMML0340B rev.1 - 03/201616