8.6.2.9 Heat Pump
Available if Controller type (LCDM)= “Unit” or “Unit + Room”.
Water Pump Conguration
Outdoor average Timer
Minimum ON Time
Minimum OFF Time
Emergency Operation
Seizure Protection
REF Access Description
Default
Value
Range Steps Units Application
Notes
Heat Pump S SC S80 M
HPWP1
Water Pump Conguration - - - - -
HPOUt
Outdoor average Timer 4 0~24 1 hour -
Rton Minimum ON Time 6 0~15 1 min -
Rtoff Minimum OFF Time 6 0~15 1 min -
HPEO Emergency Operation Manual Manual/ Automatic - - -
- Seizure Protection - - - - -
Water Pump Conguration
REF Access Description
Default
Value
Range Steps Units Application
Notes
Water Pump Conguration S SC S80 M
WPOp Operation Mode Fix ΔT/Fix - - -
WPSS Space Speed 100 50~100 5 % (*1)
WPDS DHW Speed 100 50~100 5 % (*2)
WPWS
SWP Speed 100 50~100 5 % (*3)
WPMinf
Minimum OFF Time 40 0~120 10 min -
WPMino Minimum ON Time 10 0~120 10 min -
WPOvr Overrun Time 10 0~120 5 min -
WPSc Stop conditions Standard Standard/Thermo OFF - - -
? NOTE
(*1):If Operation mode (WPOp) = “Fix”.
(*2): If Status (DHWs) = “Enabled”.
(*3): If Status (SWP) = “Enabled”.
Seizure Protection
REF Access Description
Default
Value
Range Steps Units Application
Notes
Seizure Protection S SC S80 M
HPWP1 Status Disabled Disabled / Enabled - - -
HPOUt Operation Day Monday Mon ~ Sun - day (*1)
Rton Starting Time 01:00 (00:00~ 23:50) 00:10 time (*1)
? NOTE
(*1):If Status (HPWP1)= “Enabled”.