3.5 ELECTRICAL DATA
3.5.1 Considerations
Key words:
U: Power supply.
PH: Phase.
IPT: Total input power.
STC: Starting current: Less than maximum current.
RNC: Running current.
MC: Maximum current.
? NOTE
Heating conditions: Inlet/outlet water temperature: 30/35ºC; Outdoor ambient temperature (DB/WB): 7/6ºC
The compressor data shown in the tables below are based on a combined capacity of 100% of the power supplied.
The “Maximum current” shown in the above table is the maximum total unit running current at the following conditions:
- Supply voltage: 90% of the rated voltage.
- Unit capacity: 100% at maximum operating conditions.
The power supply cables must be sized to cover this maximum current value.
Specications in these tables are subject to change without notice in order that HITACHI may bring the latest innovations to their customers.
Please refer to the general information, cautions and notes regarding protective devices (CB, ELB) throughout the “7. Electrical and control
settings” chapter.
3.5.2 Split system - Outdoor unit
RAS-(2-10)WH(V)NP(E)
Model Power supply
Applicable voltage Compressor and fan motors
MC
(A)
Max. IPT
(kW)
U max.
(V)
U min.
(V)
PH
STC
(A)
RNC
(A)
IPT
(KW)
RAS-2WHVNP
1~ 230V 50Hz 253 207 1~
-
4.9 1.13 13.8 3.14
RAS-2.5WHVNP 5.7 1.30 15.8 3.59
RAS-3WHVNP 8.3 1.88 17.8 4.05
RAS-4WHVNPE 8.9 2.02 30.5 6.93
RAS-5WHVNPE 12.8 2.91 30.5 6.93
RAS-6WHVNPE 15.9 3.61 30.5 6.93
RAS-4WHNPE
3N~ 400V 50Hz 440 360 3N~
3.2 2.02 14.0 8.70
RAS-5WHNPE 4.7 2.91 14.0 8.70
RAS-6WHNPE 5.8 3.61 16.0 9.95
RAS-8WHNPE 8.1 5.06 24.0 15.00
RAS-10WHNPE 11.2 7.03 24.0 15.00
GENERAL DATA
PMML0335A rev.1 - 04/2016
61