EasyManua.ls Logo

Holley LoRaWAN DTZ541-ZDBL - MRM data records and status; HEX-Code conversion

Holley LoRaWAN DTZ541-ZDBL
35 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User Manual LoRaWAN mME DTZ541 Three-phase electricity meter
28 / 31
Data record-1 from the mME counter
Byte-
length
14
3
2
4
2
Content
Conter number
Counter
firmware
version
Counter firmware
checksum
Adapter firmware
version
LoRaModul-
firmware-
Version
Data record-2 from the mME counter
Byte-
length
5
5
5
5
5
5
3
3
3
3
4
4
Content
1.
8.
0
1.8.1
1.8.2
2.8.0
2.8.1
2.8.2
P
sum
P
L1
P
L2
P
L3
Status
word
Second index
RFU: Reserved for future use
Status
Status-Bits
description
0
Not OK, so serious errors within the metrological
part of the measuring device
1
Meter operation OK
"Not Ok" can only be sent whenever a counter reading can be send, but is not accessible.
10.1.2 HEX-Code conversion
5 byte consumption value ( unit 0,1Wh):
E.g. 000000FFFF interprets 65,535 * 0.1 * Wh = 6553.5 Wh = 6.5535 kWh
3 byte consumption value ( unit 0,1W):
e.g. 0000FF interprets 255 * 0.1 * W = 25.5 W.
example
Payload from the counter:
1100000623CD00000623CD000000000000000000000000000000000000000000006100000000006
10000000008010400483A68