User Manual LoRaWAN mME DTZ541 Three-phase electricity meter
11 / 32
Variant 60A/100A
Phase Clamps
1, 3, 4, 6, 7, 9, 10, 12
Voltage /
N tap
2, 11
Additive -
Clamps
13, 15, 27, 28
Clamps (mm)
9,5
3,0
3,0
Min. Connection cross-sections
(mm²)
6
1,5
1,5
Max. Connection cross-sections
(mm²)
35
2,5
2,5
Prescribed tightening torque (Nm)
1,52,5
0,5
0,5
Kopf
PZ2
Kreuzschlitz
Kreuzschlitz
Thread size
M6
M3
M3