MAN0530 Issue 15 - 07/17 Searchline Excel
2104M0506
Conduit seal
required
(see OEM J/B details)
7. CERTIFICATION
7.4 CSA/FM
FM Approval
Complies with ANSI/ISA-12.13.04/FM6325 for Methane, Ethane, Propane and Butane (Short
Range, Medium Range and Long Range Open Path Systems)
7.4.1 Transmitters
7.4.2 Receivers
CSA approved
M20/0.5in. NPT adaptor
IS Cable
Length 15m max.
DX100/DX100(M) CSA
Termination Unit
Class I Div 1
GroupsB,C,D
(Tamb -55 to +40 C)
o
SHC1 Handheld
Interrogator
Class I Div 1
GroupsB,C,D
(Tamb -55 to +40 C)
o
Receiver
Class I Div1GroupsB,C,D
T5 and Exd IIC T5
(Tamb -40 to +65 C)
o
Flexible conduit -
must conform with the relevant
Canadian installation codes of practice
(see Control Drawing 2104E0097)
(customer supplied)
CSA Receiver:
Class I Div 1 Groups B, C,
D, T5 & Exd IIC T5
(Tamb-40to+65
o
C)
DX100/DX100(M) CSA/FM
Termination Unit Class I Div 1
Groups B, C, D
(Tamb-55to+40
o
C)
SHC1 Handheld
Interrogator CSA/FM
Class I Div 1
Groups B, C, D
(Tamb-40to+65
o
C)
FM Receiver:
Class I Div 1
Groups
B, C & D
(-40to+65
o
C)
CSA approved
M20/0.5in. NPT adaptor
Note: Later units
1
/
2
" NPT
threaded without adaptor
Flexible conduit (customer supplied) -
must conform with the relevant US and
Canadian installation codes of practise
(conduit seal required within 30" of transmitter)
IS Cable Length
15m max.
Conduit
seal
required
within
6" of enclosure
(see OEM
J/B details)
CSA Transmitter:
Class I Div 1 Groups B, C & D T5
andExdIICT5(Tamb-40to+65
o
C)FM Transmitter:
ClassIDiv1,GroupsB,C&D(-40to+65
o
C)
CSA/FM approved
explosion proof junction
box
CSA approved
M20/
1
/
2
NPT threaded
without adaptor Note:
Later units
1
/
2
" NPT
threaded without adaptor
Flexible conduit (customer supplied) -
must conform with the relevant US and Canadian
installation codes of practice (conduit seal required
within 30" of transmitter)