96
MAN0530 Issue 15 - 07/17 Searchline Excel
2104M0506
Provided that the SIG level is greater than the TGT level, the signal check should pass on to
the next stage of installation.
Initialisation
This starts the initialisation process. The following message is displayed:
Press Enter to
Initialise Unit
This message is displayed during the initialisation process after pressing Enter.
Processing Data
Please Wait
This message is displayed for three seconds at the end of a successful initialisation process.
Unit Initialised
Note: The Searchline Excel system is live after a successful initialisation.
Set Time
This option lets you set the system’s time and date.
The initial display after SET Time is chosen is in the following format:
Time HH:MM
hh:mm
where: hh Hours.
mm Minutes.
Whenrstdisplayedonlythecurrenthourisshown.
All settings are adjusted by means of the
and keys on the keypad.
After setting the hour the minutes are displayed.
After the time has been entered then the same process is used to set the date which is displayed
in the following format:
Date DD/MM/YY
dd/mm/yy
where: dd Day.
mm Month.
yy Last two digits of the year.
>
>
>
>
APPENDIX A - HANDHELD INTERROGATOR