97
MAN0530 Issue 15 - 07/17 Searchline Excel
2104M0506
Notes:
1. The time and date will not be updated unless both are entered and accepted without
error.
2. The year 2000 is displayed as 00.
Cal Sensor
This menu option zeros the system.
Notes:
1. The 4-20 output is inhibited during this procedure. See the earlier description.
2. There must be no gas in the system beam path whilst this procedure is carried out.
The following message is displayed:
Ensure Zero Gas
Press Enter
The following message is displayed while the calibration operation is being performed:
Processing Data
Please Wait...
If the calibration is successful, the following message is displayed for a period of three
seconds:
Zero Calibrated
Force mA
Thisoptionallowsthesystem’sanalogueoutputsignaltobeadjustedtoaxedlevel,e.g.when
setting up a system controller. The following message is displayed:
O/P current mA
mmmmm
where: mmmmm Current to output.
This is adjusted using the
and keys over the range 1mA to 21mA in steps of 0.1mA.
After adjustment the output is forced to the set level and the following message is displayed:
Fixed: mmmmm mA
Press Enter
where: mmmmm Analogue output current previously set.
>
>
APPENDIX A - HANDHELD INTERROGATOR