Figure 3. 5817CBXT Transmitter, Top Cover Removed
NOTE: For UL commercial and household fire installations, only one
initiating device may be connected to this transmitter. For UL
commercial burglary installations, multiple initiating devices may be used
as long as the devices all serve the same function, such as door/window
contacts, motion or glassbreak detectors. All initiating devices must be
located within the same room.
No more than one wire per terminal may be connected.
Use only 14-22AWG wire.
BATTERY INSTALLATION/REPLACEMENT
1. Remove the transmitter's cover as described in Mounting Step 2.
2. Observe correct polarity and insert the battery provided into the
battery holder (see Figure 3). Take care not to bend the antenna.
Note: Replace battery only with: Duracell DL123A, HUIDERUI
CR123A, Panasonic CR123A or Resideo 466.
!
Risk of fire, explosion, and burns. Do not recha
rge, dis
-
assemble, heat above 212°F (100°C), or incinerate. Dispose
of used batteries promptly. Keep away from children.
3. To replace the cover, engage the hooks along the top edge and
snap shut. Install cover locking screws when required for regulatory
agencies.
ENROLLMENT NOTE: Wait 30 seconds after battery installation before
enrolling transmitter.
NOTE: Constant exposure to high or low temperature or high humidity
may reduce battery life.
TESTING
Regular maintenance and inspection (at least annually) by the installer
are vital to continuous satisfactory operation of any alarm system. The
installer should instruct the user to test the system frequently (at least
weekly) to insure the system's operation at all times, as well as offer a
regular maintenance program to the user. The user should also be
acquainted with proper operation and limitations of the entire alarm
system. For testing procedures, refer to the User Guide or Installation
and Setup Guide for the system control panel.
UL Requirement
1. If using a compatible commercial control panel (ex. VISTA Turbo
series) and programming the 5817CBXT as an Entry/Exit zone, you
must enroll the tamper loop (loop 4) as a separate zone,
programmed for 24-hour response (e.g., Zone type 5 Trouble-by-
day/Alarm-by-night).
2. For UL Commercial Burglary installations, this transmitter must be
used in conjunction with the 5881ENHC RF Receiver.
SPECIFICATIONS
U
L
For dry, indoor use only. Do not install in air-handling spaces
Dimensions: 1-9/16"W x 3-1/2"H x 1-3/16"D (40mm x 89mm x 30mm)
Battery: 3V Lithium (see BATTERY INSTALLATION/
REPLACEMENT).
Signal Level: To determine ambient noise level and signal strength,
refer to compatible receiver Installation and Setup
Guide.
NFPA-72 Compliant.
UL Listings:
Commercial Fire: UL864
Household Fire: UL985
Household Burglary: .UL1023
Commercial Burglary: UL365, UL609, UL634, UL1076, UL1610
TO THE INSTALLER
Regular maintenance and inspection (at least annually) by the installer and
frequent testing by the user are vital to continuous satisfactory operation of
any alarm system. The installer should assume the responsibility of
developing and offering a regular maintenance program to the user, as well
as acquainting the user with the proper operation and limitations of the
alarm system and its component parts. Recommendations must be
included for a specific program of frequent testing (at least weekly) to insure
the system’s operation at all times.
FEDERAL COMMUNICATIONS COMMISSION STATEMENTS
The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual. Unauthorized
changes or modifications could void the user's authority to operate the equipment.
FCC/IC NOTICE: This device complies with Part 15 of the FCC Rules, and RSS-210 of IC. Operation is subject to the following two conditions: (1) This
device may not cause harmful interference (2) This device must accept any interference received, including interference that may cause undesired operation.
Cet appareil est conforme à la partie 15 des règles de la FCC & de RSS-210 des Industries Canada. Son fonctionnement est soumis aux conditions
suivantes: (1) Cet appareil ne doit pas causer d' interférences nuisibles. (2) Cet appareil doit accepter toute interférence reçue y compris les interférences
causant une réception indésirable.
REFER TO THE INSTALLATION INSTRUCTIONS FOR THE CONTROL WITH WHICH THIS DEVICE IS USED, FOR DETAILS REGARDING LIMITATIONS OF THE
ENTIRE ALARM SYSTEM
.
Responsible Party / Issuer of Supplier’s Declaration of Conformity: Ademco Inc., a subsidiary of Resideo Technologies, Inc., 2 Corporate Center
Drive., Melville, NY 11747, Ph: 516-577-2000
The product should not be disposed of with other household waste. Check for the nearest authorized collection centers or authorized recyclers. The
correct disposal of end-of-life equipment will help prevent potential negative consequences for the environment and human health.
Any attempt to reverse-engineer this device by decoding proprietary protocols, de-compiling firmware, or any similar actions is strictly prohibited.
SUPPORT & WARRANTY INFORMATION
For the latest documentation, support and warranty information, please go to:
www.resideo.com
This product manufactured by Resideo Technologies Inc. and its affiliates
Ê800-18448E
800-18448E 5/14 Rev. E
2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
2020 Resideo Technologies, Inc.
www.resideo.com

Other manuals for Honeywell ADEMCO 5817CBXT

Related product manuals