Installation and Setup Guide
5-22
Configurable Zone Type Programming (*83 Menu Mode)
Start Configurable Zone Type Programming Mode by pressing
83
while in Data Programming mode.
PROMPT
VALID ENTRIES EXPLANATION
Enter Zone Type
(00=quit) 90
Zone Type Number
90-93 = zone type
[] to continue
Enter the configurable zone type number being
programmed.
90 Zn Attributes
0
Zone Attributes
0 = none
1 = exit delay only
2 = entry/exit 1
3 = entry/exit 2
4 = follows entry/exit
5 = has verification (resets
power upon event and when
code + OFF to clear condition. If
condition persists, zone
activates)
6 = resettable (upon code + OFF)
[] to continue
Enter the desired zone attributes.
NOTE: If 6 is selected for the Zone Attribute,
enter 0 for Alarm/Trouble Processing at the below
Alm/Trbl Proc prompt.
90 Bypass Option
0
Bypass Option
0 = zone type cannot be
bypassed
1 = auto bypassed when armed
in stay mode
[] to continue
Enter the desired bypass option.
90 Resp to Short
Armed 0 DArmd 0
Response to Shorts
0=none 2=trouble
1=Alarm 3=fault
[] to continue
Select the type of response when zones assigned to
this zone type are shorted when the system is
armed.
NOTES: 1. For double-balanced zones, this entry
must be 0.
2. For zone-doubled zones, both zones of
the doubled pair must be assigned the
same response to a short.
90 Resp to open
Armed 0 DArmd 0
Response to Opens
0 = none 2 = trouble
1 = Alarm 3 = fault
[] to continue
Select the type of response when zones assigned to
this zone type are opened when the system is
armed.
90 Vent Zone
0 = No, 1 = Yes
Vent Zone?
0=no
1=yes
[] to continue
If selected, the system can be armed even if zones
assigned to this zone type are faulted.
NOTE: After arming, faults on these zones will be
ignored until the zone is restored.
90 Alm/Trbl Proc
0
Alarm/Trouble Processing
0=none
1=Zone type has automatic
restore
2=zone type uses Misc. Fault
Delay Time and automatic
restore
[] to continue
Select desired actions for zones assigned to this
zone type.
Option 2: Select Miscellaneous Fault Delay in
field *87.
NOTE: If 6 was selected above for the Zone
Attribute, enter 0 for this prompt.