AQ25A SERIES PROGRAMMABLE BOILER CONTROL PANELS
15 69-2119—02
When you finish setting the DIP switches for all the Zoning
Modules, replace the front cover of the AQ25A Control Panel
and the cover of each Expansion Zoning Panel.
NOTE: The snap-on DIP switch covers are designed so they
cannot be removed (exposing the DIP switches)
when the front cover of the AQ25A Control Panel is in
place.
Table 2. AQ15540B Zoning Module (Pump Zoning Module) DIP Switch Arrangement.
DIP
Switch Switch Description Label and Factory Settings
1
2
3
4
Zone Address: The positions of these 4 DIP switches define the unique address for
each zone on the AQUATROL network. For each group of 4 zones, there can be only
one DIP switch in the right hand (ON) position.
The correct DIP switch settings for each zone module are:
• First Zone (1-4) Module: 1 = ON position; 2, 3, and 4 = OFF position
• Second Zone (5-8) Module: 2 = ON position; 1, 3, and 4 = OFF position
• Third Zone (9-12) Module: 3 = ON position; 1, 2, and 4 = OFF position
• Fourth Zone (13-16) Module: 4 = ON position; 1, 2, and 3 = OFF position
5
• If set to SYNC, zone synchronization is enabled.
• If set to NOT, zone synchronization is disabled.
6
• If zone valves are normally closed (N.C.), set the NC/NO DIP switch to the OFF
position.
• If zone valves are normally open (N.O.), set the NC/NO DIP switch to the ON
position.
7
• If set to Group (ON position), the AUX Pump contacts on the Control Module are
switched when any of the zones on this Zoning Module are active.
• If set to - (OFF position), the AUX Pump contacts are not affected by activity on
these zones.
8
• If set to 2-stage (ON position), then 2-stage operation is activated on thermostat
inputs. The zoning module operates as two 2-stage zones.
• If set to 1-stage (OFF position), then operates as four 1-stage zones.
Diagnostic
Test
Diagnostic
Test
M2769
ON
12345678
M23720
AQ15540B