BC-200 Networking is accomplished using a series of modules and products which allow a group of Fire Alarm
Control Panels (FACP) and other control equipment to connect, forming a true peer-to-peer network. Equipment
that connects to network and communicates with other equipment using the network may be referred to as a
network node. The minimum hardware requirement for network is two nodes connected via wire (or optical fibre).
Network for the BC-200 supports up to 100 nodes. The BC-200 occupies a single node address on the network.
Each network node requires a unique node address; the node communicates with other nodes via a Network
Control Module (NCM). The NCM connects to the BC-200 via the Network Interface Module (NIM).
9.6.5.1 NETWORK INTERFACE MODULE (NIM)
To Network Interface Module
40 WAY
RIBBON
CABLE
MAIN TERMINATION BOARD (FIM)
J3
Ribbon cable to LIM (If fitted)
(termination board)
from FIM (termination
board)
(NUP port on IFS-725)
Not used on NIM
to LCM/LEM boards
Factory programming port
Reset Switch
Address Settings
Network Interface Module
NIM connects to the NUP port on the NCM.