EasyManua.ls Logo

Honeywell BC-200 - Service Menu - Lists

Honeywell BC-200
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Panel Operation
BC-200 Manual P/N DOC-01-013 28
7
7
.
.
3
3
.
.
3
3
S
S
E
E
R
R
V
V
I
I
C
C
E
E
M
M
E
E
N
N
U
U
L
L
I
I
S
S
T
T
These menus allow access to various information lists. List Menu 1 is shown first. Use the PREV and NEXT
buttons to scroll through the options then use SELECT to select the currently highlighted option or use the
numeric keypad. Item (6) on List Menu 1 (LIST) will move you to List Menu 2. The MENU button will return you
to the Service Menu. The available lists are:
1) ALARM DISPLAY ALARMS
2) FAULT DISPLAY FAULTS
3) ISOLATED DISPLAY ISOLATED POINTS
4) ACTIVE DISPLAY ACTIVE/NON-ALARM
5) PREALARM DISPLAY PREALARMS
6) LIST DISPLAY 2800 POINTS
7) HISTORY DISPLAY SYSTEM HISTORY
8) SHADOW DISPLAY SHADOW HISTORY
LIST MENU 1
20 JULY 2002 14:44:37
DOWNUP
MENU
USE BUTTONS/NUMBERS TO SELECT A FUNCTION
A = 0
F = 0
I = 0
N = 0
SELECT
DAY MODE
1) ZONE DISPLAY ZONE GROUPS
2) AZF DISPLAY ALARM ZONES
3) DOUT DISPLAY DIGITAL OUTPUTS
4) DIN DISPLAY DIGITAL INPUTS
5) VIRTUAL DISPLAY VIRTUAL POINTS
6) NETPOINT DISPLAY NETWORK POINTS
7) ANALOG DISPLAY ADDRESSABLE POINTS
8) RING DISPLAY AVAILABLE RINGS
LIST MENU 2
20 JULY 2002 14:44:37
DOWNUP
MENU
A = 0
F = 0
I = 0
N = 0
SELECT
DAY MODE
USE BUTTONS/NUMBERS TO SELECT A FUNCTION
Menu Item Explanation
ALARM Displays all current alarms on the system in chronological order and allows you to
acknowledge reset and isolate alarmed points using the soft buttons.
FAULT Displays all current faults on the system in chronological order, and allows you to acknowledge,
reset and isolate fault points using the soft buttons
ISOLATED Displays all currently isolated points on the system and provides a soft button for de-isolation.
ACTIVE Displays all active Non-Alarm events on the system in chronological order and allows you to
acknowledge, reset and isolate points using the soft buttons.
PREALARM Displays all active Pre-Alarm events on the system in chronological order and allows you to
acknowledge, reset and isolate points using the soft buttons.
LIST Moves you to List Menu 2 with the menu items listed below
HISTORY Displays the systems history event buffer in chronological order.
SHADOW Displays the systems shadow history event buffer in chronological order.
ZONE Display zones as per AS4428. Allows editing of displayed zone names for Fire-fighters display
purposes.
AZF Displays all system AZF’s and shows current status. Soft Buttons provide ability to Test and
Change a points programming.
DOUT Displays all system Digital Outputs (Relays & LEDs) and shows current status. Soft Buttons
provide ability to Test and Change a point’s programming.
DIN Displays all system Digital Inputs and shows current status. Soft Buttons provide ability to Test
and Change a point’s programming.
VIRTUAL Displays all system Virtual Points. Soft Buttons provide ability to change a point’s
programming.
NETPOINT Displays all system Netpoints. Soft Buttons provide ability to change a point’s programming.
ANALOG Displays Analog addressable loops and detectors/modules with names for status viewing,
editing and testing.
RING Displays the systems communications rings and modules found on each.