Appendix
BC-200 Manual – P/N DOC-01-013 95
9.2 PASSWORD ACCESS LEVELS
The BC-200 has 3 levels of password protection. For a full explanation of how to use passwords, refer to 77.
Each password level can have 5 different user passwords and each password level has security access as
follows:
Level 0 (no Password Required)
Firefighter’s Screen
Ability to reset alarms
Ability to reset faults
Ability to isolate / de-isolate
Ability to view system information
Ability to view history
Ability to view all read-only data
Level 1
Level 0 access +
Ability to change descriptors
Ability to change point options
Ability to change display zone options
Ability to add and edit pushbutton isolate
functions.
Ability to change global options
Ability to alarm and fault test devices
Level 2
Level 1 access +
Ability to add and remove modules/devices
Ability to change scripts
Ability to auto-program Analog
addressable loops
Level 3
Level 2 access +
Ability to perform upload/download
Ability to delete history
Ability to change passwords
Ability to access diagnostics menu